|
.... |
| LP-Gas Tank Vapor
Manifolds It has been a long-standing industry practice to manifold two or more
storage tanks together in order to increase a gas systems vaporization capacity.
Often, a commercial account makes significant facility renovations and additions
adding gas load. Rather than pumping out and removing existing storage tanks in favor of a
single and larger tank, the retailer simply adds an additional tank (or tanks) to meet the
new gas demand. This is a common practice. There are many factors to consider when
manifold systems are constructed.
This bulletin provides installation tips for the
manifolding of storage tanks used for vapor withdrawal. It does not cover tanks used for
the purpose of liquid withdrawal such as dispensing systems, vaporizer service, etc. The
piping and valve requirements for such systems are significantly different than those in
vapor systems. Therefore, the information provided in this bulletin may not apply. It is the responsibility of the gas retailer to verify compliance
with any local codes and ordinances which may apply, including NFPA 58 Liquefied Petroleum
Gas Code.
Section I: Setting the Tanks
- Tanks must be set on a firm footing and must be properly supported
to comply with NFPA 58.
- The maximum filling liquid level of each tank in a multi-tank
installation should be on the same elevation.
- Distance requirements between each container, property lines,
buildings, etc. can be found in NFPA 58 and must be followed.
Section II: Constructing the
Manifold
- Construct the manifold in such a way that it helps to prevent
condensate from accumulating and interfering with proper regulator operation.
- An excess flow valve must be installed on the outlet side of each
tanks vapor withdrawal valve. Excess flow valves are available with M.POL by NPT
connections.
- Connect one end of a suitable connector, such as copper tubing to
the outlet side of the excess flow valve. Connect the other end to the manifold as
illustrated.
- All threaded piping leading in to the first stage regulator must be
schedule 80. All fittings must be 250 PSI min.
- Install the first stage regulator with the vent pointing down,
and/or under a protective cover. Be sure that the regulator is adequately supported.
- On underground tanks the regulator may be installed inside one of
the tank domes, or a regulator housing box may be used. Install the regulator so the vent
is above the highest possible water level.
- Manifold piping should be of adequate size to supply the gas load
during peak demand.
Section III: Start Up
- After the final connection has been made, leak test the entire
system for compliance with established company procedures, all local codes, and NFPA 58.
For more information, see NFPA 54, the National Fuel Gas Code, NFPA 58, and RegO Products
LP-Gas Service Manual L-545.
- Properly purge any residual air or inert gas from the system. See
NFPA 54 and NPGA Safety Bulletin # 410-92.
- Set up system according to appliance or equipment
manufacturers instructions. Properly adjust all regulators according to appliance or
equipment manufacturers instructions. Do not exceed regulator delivery pressure
limits specified in NFPA 58.
- If the system does not function properly, close all valves,
including those at the tanks, and contact supervisor.

|
|
|